<think>.pdf

2017-11-27_Rubinetto_Circolo_Acli_fraz_Villa_DAria.pdf
Preview of <think>
🔗 Source: assm.it
📊 Size: 44 KB
📄 Pages: 2 pages
⬇️ Downloads: 1,349

Summary

Let me start by reading through the content carefully.

The document is a "RAPPORTO DI PROVA" (Test Report) from the Agenzia Regionale per la Protezione Ambientale delle Marche, specifically the Dipartimento Provinciale di Macerata - Servizio Laboratoristico. The report number is MDDG167r03, dated 01/07/2017, but the analysis dates are from 27/11/2017 to 30/11/2017. The sample is water from the distribution network, with the sample number 2212/PT/17A. It was collected by ASUR AV 3 MACERATA, managed by ASSM SPA - TOLENTINO, located at RUB. CIRCOLO ACLI in Serrapetrona, specifically in the Frazione Villa d'Aria. The requestor is ASUR MARCHE, Area Vasta N.3 - SIAN MACERATA.

The report includes various chemical and biological parameters tested. For chemical parameters, the methods are specified with APAT CNR IRSA standards. The results are given with measured values, uncertainties, detection limits, and upper limits. For example, free chlorine is 0.09 mg/l with an uncertainty of ±0.8 mg/l, detection limit 0.05 mg/l, and upper limit 0.2 mg/l. Conductivity is 350 µS/cm, pH is 7.4, fluorides 0.07 mg/l, chlorides 8.9 mg/l, etc. Some parameters like turbidity have an "ILD" (Inferiore al limite di determinazione), meaning below the detection limit.

Biological parameters include Escherichia coli, coliforms, enterococci, and colony count on agar at 22°C. All these are reported as 0 U.F.C./100 ml, which is zero colony-forming units per 100 ml, indicating no presence of these microorganisms.

The uncertainty is mentioned as expanded uncertainty, calculated by multiplying the standard uncertainty by a coverage factor K=2, giving 95% confidence. The report also states that the tests are not part of the ACCREDIA accreditation, so the results aren't certified by that body. The report is issued on 30/11/2017 and is for the specific samples tested. It can't be reproduced partially without written approval from the testing laboratory.

I need to make sure the summary includes all the key points: the report's purpose, the sample details, the parameters tested, their results, the uncertainty and detection limits, and the note about accreditation. Also, the dates of analysis and the responsible person. I should avoid any markdown and keep it in Italian, as per the user's request. Let me structure this in a clear, concise manner without adding extra information. Check for any missing details and ensure all parameters are covered. Make sure to mention that some parameters were below detection limits. Also, note the methods used and the standards referenced. Finally, confirm the issuance date and the non-accreditation note.

RAPPORTO DI PROVA MDDG167r03, emesso il 30/11/2017, riguarda il campione d'acqua in rete di distribuzione n. 2212/PT/17A prelevato il 27/11/2017 in Serrapetrona (Frazione Villa d’Aria), gestito dall’ASSM SPA - TOLENTINO. I test, condotti dal 27/11/2017 al 30/11/2017, includono analisi chimiche e biologiche secondo metodi APAT CNR IRSA e standard UNI EN ISO. I parametri chimici (cloro residuo libero, conducibilità, pH, fluoruri, cloriti, fosforo, solfati, sodio, azoto ammoniacale, potassio, magnesio, calcio, durezza totale) sono riportati con valori misurati, incertezza tipo ± (K=2, 95% di confidenza) e limiti di determinazione. Alcuni parametri (es. torbidità, cloriti, fosforo, azoto ammoniacale) sono inferiori al limite di determinazione (ILD). I parametri biologici (Escherichia coli, coliformi, enterococchi, contatto colonie su agar) mostrano risultati zero U.F.C./100 ml. Il rapporto non è accreditato ACCREDIA e non può essere riprodotto parzialmente senza autorizzazione.

Description

Document en it

Technical Information

  • File Format: PDF
  • File Size: 44 KB
  • Pages: 2
  • Language: IT
  • Total Downloads: 1,349
  • Last Updated: 2 hours ago

Document Overview

This PDF document about <think> provides comprehensive information and guidance. Whether you're a beginner or advanced user, this resource offers valuable insights into <think>.

Related Topics

If you're interested in <think>, you might also want to explore:

Download eBooks for free and learn more about . These books contain exercises and tutorials to improve your practical skills, at all levels!

Not satisfied with this document? We have related documents to , try searching with similar keywords: PDF Whatever You Think Think The Opposite, Free Exchange Nudge Nudge Think Think The Economist, How To Hack Think Points To Think Through Math, Moms Who Think Moms Who Think, Paul Arden Whatever You Think Think The Opposite Free Download, Stop Take Some Time To Think Think About Whats Important To You, Think Definition Of Think By The Free Dictionary, Think Fast Think Slow

You can download PDF versions of the user's guide, manuals and ebooks about , you can also find and download for free A free online manual (notices) with beginner and intermediate, Downloads Documentation, You can download PDF files (or DOC and PPT) about for free, but please respect copyrighted ebooks.