Specifications are subject to change without notice. These products are not intended for use as critical components in life support or nuclear systems.
ODX-6000
6000 VA DC/AC Inverter
General Features:
Sine wave output voltage
Suitable for motors control
Adjustable output frequency
Adjustable output voltage
High input-output isolation 3000 Vrms
Remote off opto-coupled
Alarm by isolated relay contacts
Configurable input: Reverse or Mid power
Remote control via RS232
CAN BUS (optional)
Parallelable output (optional)
Railway version EN50155 (optional)
Fire and smoke: EN45545-2 approved
Input Voltage Range: -30, +25% Vin nom
Maximum Input Ripple: 5% Vin nom (Vrms, 100 Hz)
Output Nominal Voltage (Von): See table
Output Voltage Range: 20…100% of Von (adjust via remote control)
Output Frequency: 50 / 60 Hz via DIP-switch, 5…75 Hz via RS-232
Load Regulation: < 4.5%
Line Regulation: < 2% Vin -25% … +25%
< 10% Vin -30% … +30%
< 20 % Vin -40 % … +40 % (100ms)
Output Wave Distortion THD: < 2% (average of 16 samples)
Output HF Ripple: < 2.5%
Environmental:
Storage Temperature: -40 … 80 °C
Operating Temperature: Full load -40 … 55 °C (EN50155 OT2), -40 … 70 °C (EN50155 OT4)
Relative Humidity without Condensation: 5 … 95%
Maximum Altitude: 2000m at full load, 2500m at 95% of load
Cooling: Internal controlled internal fan
EMC:
Immunity according EN61000-6-2, EN50121-3-2
Emissions according EN61000-6-4, EN50121-3-2
Safety:
Dielectric strength: Input /output 3000 Vrms / 50 Hz / 1 min
Dielectric strength: Output / Earth 1500 Vrms / 50 Hz / 1 min
Dielectric strength: Input / Earth 500 Vrms / 50 Hz / 1 min
Safety according to EN60950-1, EN62368-1
Fire and smoke: EN45545-2 approved (only for option T, railway version)
Mechanical:
Weight: < 8950 g
Protection degree: IP20
Protections:
Against overloads: Current and I²T limited (see overload protection curve)
Against over-temperature: Shutdown with auto-recovery
Control:
Output OK LED: Green
Input OK LED: Green
Alarm LED: Red
Input alarm: Open when alarm. Maximum rating: 0.16 A at 160 Vdc
Output alarm: Open when alarm. Maximum rating: 0.16 A at 160 Vdc
Remote OFF input: OFF applying 15…143 Vdc (acc. to EN50155), Impedance > 35 kΩ
Configurable input (reverse or mid-power): ON: applying 15…143 Vdc (acc. to EN50155), Impedance > 35 kΩ
Ordering Codes:
Model Input Voltage Range Max. Input Current Output Voltage AC Output Current Active Output Power Appar. Output Power [VA] Output Peak Current Efficiency [%] No load input current [A] (5s) (Iopk) [A] (10ms)
ODX-6000-7502 24 16.8 - 30 232 400 6.50 3500 4500 7.8A 20 91.0 1.70
ODX-6000-7505 48 33.6 - 60 191 400 8.66 6000 6000 11.5A 20 93.6 0.85
ODX-6000-7506 72 50.4 - 90 127 400 8.66 6000 6000 11.5A 20 94.3 0.58
ODX-6000-7507 110 77 - 138 83 400 8.66 6000 6000 11.5A 20 94.2 0.38
Option P (Parallelable) includes CANBUS port.
Option K (Motor breaking) allows a motor to slow down faster. It includes internal resistors to dissipate energy from the motor; up to 1200 Wpk and 800 W for 5 s. This option includes CANBUS port.
Please check availability for P, K or N options. Accessories must be ordered in a separate order line.
BLOCKS DIAGRAM
CONNECTIONS
J1 -Vin Terminal M8 (Max 4.8 Nm)
J2 +Vin
J5 - 1 Protective Earth
J5 - 2 Output R
J5 - 3 Output S
J5 - 4 Output T
J5 - 5 Output Neutral
J4 - 1 + Configurable input
J4 - 2 - Configurable input
J4 - 3 + Remote
J4 - 4 - Remote
J8 - 1, 2 Output alarm
J8 - 3, 4 Input alarm
J7 - 1 CAN L (optional Can bus)
J7 - 2 CAN H (optional Can bus)
J7 - 3 GND CAN
J3 - 2 RS-232 Rx
J3 - 3 RS-232 Tx
J3 - 5 RS-232 GND
J3 rest Not connected
J6A - J6B Optional Parallel operation RJ45
SW1 - 1 Master / Slave
SW1 - 2 Parallel / Stand alone
SW1 - 6 Local / Remote
SW1 - 7 50 Hz / 60 Hz